Mitsubishi 9800A Series Specifiche

Navigare online o scaricare Specifiche per Alimentatori Mitsubishi 9800A Series. Mitsubishi 9800A Series Specifications [en] Manuale Utente

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 20
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 0
Keyitec, Inc. Tel.: 480-563 4172 Fax: 480-563 4997 e-mail: [email protected] Rev 1.0 10/00
MITSUBISHI UPS SYSTEMS
MITSUBISHI UPS
9800 SERIES
SINGLE MODULE SYSTEM
SPECIFICATIONS
Vedere la pagina 0
1 2 3 4 5 6 ... 19 20

Sommario

Pagina 1 - MITSUBISHI UPS SYSTEMS

Keyitec, Inc. Tel.: 480-563 4172 Fax: 480-563 4997 e-mail: [email protected] Rev 1.0 10/00

Pagina 2 - TABLE OF CONTENTS

8 4.1.3. Automatic Input Walk-in The Rectifier logic shall employ circuitry to allow a delayed and timed ramping of input current. Subsequent to en

Pagina 3 - 2. SYSTEM DESCRIPTION

9 the specified float level). Upon completion of the timer count, the Rectifier output voltage shall return to the specified float voltage (typically

Pagina 4

10 The Inverter output voltage shall not deviate by more than +/- 1% RMS due to the following steady state conditions: a. 0 to 100% loading. b.

Pagina 5

11 providing redundancy and, in the event of a failure, prevent unnecessary damage to power transistor components/fuses. Load current above 150% shal

Pagina 6

12 4.4.2. Automatic Re-transfers In the event that the critical load must be transferred to the bypass source due to an overload, the UPS system

Pagina 7

13 5.2. Remote Operation Certain UPS controls shall, as standard equipment, be capable of being operated from a remote location. The remote functi

Pagina 8

14 d. UPS startup e. Transfer of load to static bypass. f. Equalize charge to system battery. 5.4.2. Microprocessor Controlled Metering All m

Pagina 9 - 4. FUNCTIONAL DESCRIPTION

15 The UPS control logic power supply shall employ a redundant design utilizing the UPS utility input and the inverter output source. 7. UPS S

Pagina 10

16 8. OPTIONAL EQUIPMENT 8.1. Remote Status Alarm Panel (RSAP) The UPS manufacturer shall offer a Remote Status Alarm Panel which shall not allow

Pagina 11

17 Forced air cooling shall be provided to allow all components to operate within their rated temperature window. Thermal relays, using a latched c

Pagina 12

TABLE OF CONTENTS 1.1.1.1. SCOPESCOPESCOPESCOPE...

Pagina 13

18 M. Transfer switch operation 9.7. Eyebolts Eyebolts shall be installed as standard for lifting UPS. Four (4) heavy duty eyebolts will be install

Pagina 14 - 5. OPERATOR CONTROL PANEL

1 1. SCOPE 1.1. The System This specification describes an on-line, three phase, solid-state, uninterruptible power system, hereafter known as th

Pagina 15

2 j. Automatic UPS restart and load pick-up (after system battery depleted; AC restored). k. Programmable external customer contacts (A-Type) dry co

Pagina 16 - 6. CONTROL LOGIC POWER

3 inverter and bypass is not accomplished. The use of the static switch shall not be required during the manual or automatic re-transfer process, thu

Pagina 17 - 7. UPS STATUS INTERFACING

4 3.2.1. Nominal input voltage: 480, 600 V, 3 phase, 3 wire. 3.2.2. Input voltage range: +15%, -15%. 3.2.3. Input frequency and range: 60 Hz ±

Pagina 18 - 9. MECHANICAL DESIGN

5 3.4.6. Output frequency slew rate (inverter synchronized to static bypass): 1 Hz, 2 Hz or 3 Hz/second (selectable). 3.4.7. Free running output

Pagina 19

6 b. Recommended operating range: 30% to 90%. 3.5.6. Heat dissipation (at 100% load). a. XX kBTU/hr b. XX kW 3.5.7. Acoustical noise level:

Pagina 20

7 The system battery shall be sized to provide the specified back-up time to the inverter when the UPS is supplying 100% rated load. The battery sh

Commenti su questo manuale

Nessun commento