17
2. Replacement of FX2N series
1
Introduction
2
Replacement
of FX2N series
3
Replacement
of FX2NC
series
4
Program
changeover
method
A
Models affected
by production
termination
B
Related
manuals
C
Frequently
asked
questions
Table 1. Cable size of European type terminal connectors
For connection with RS-485 communication equipment, use a twisted pair cable with shielding.
Conforming wire size and tightening torque are as follows.
Wire size
of one-wire
connection
Wire size
of two-wire
connection
Wire ferrule
with insulation
sleeve
(wire size)
Tightening
torque
Insulation
sheath
stripping
length
*
FX2N-485-BD AWG26 to AWG16 Not usable 0.6N·m 6mm
FX2NC-485ADP
AWG26 to
AWG16
AWG26 to
AWG20
Not usable 0.4 to 0.5N·m 8mm
FX
3U-485-BD
FX3U-485ADP(-MB)
AWG22 to
AWG20
AWG22
Usable
(AWG22 to
AWG20)
0.22 to 0.25N
·
m
9mm
* Insulation sheath stripping length shows the dimension when connecting the wire to the terminal
directly.
For details, please refer to the FX Series User’s Manual (Data Communication Edition) JY997D16901.
Commenti su questo manuale