GOT-F900 SERIES (CONNECTION) Specifications 3
3-29
1
Introduction
2
Outline
3
Specifications
4
installation
and Wiring of
F940GOT
5
installation
and Wiring of
Handy GOT
6
Connection of
Peripheral
Equipment
7
Connection of
Two or More
GOT Units
8
Connection of
MELSEC-F FX
Series PLC
9
Connection of
MELSEC-A
Series PLC
10
Connection of
MELSEC-QnA
Series PLC
*1 When the power is turned on, the current consumption of 750 mA/24V DC maximum is applied.
*2 0 to 50
×
C when the screen is installed laterally. 0 to 40
×
C when the screen is installed longitudinally or horizontally.
*3 0 to 40
×
C when the extension interface is used.
*4 The life of the backlight above indicates the value at 25
×
C.
*5 Between all power terminals of the PLC and ground terminal.
*6 The relevancy is confirmed in the test for IP65f or IP54. However, this test result does not provide any guarantees that
the product stands against use in all sorts of environment.
*7 As regarding the front panel
F930GOT F920GOT-K Handy GOT
F930GOT-BWD-E F920GOT-BBD-K-E F920GOT-BBD5-K-E F940GOT-SBD-(R)H-E F940GOT-LBD-(R)H-E
5V DC
Supplied from PLC
24V DC+10%-15%
(separately prepared DC power supply)
200mA/24V DC
80mA/24V DC
(70mA/24V DC)
220mA/5V DC
(180mA/5V DC)
300mA/24V DC
(200mA/24V DC)
Built-in (irreplaceable)
−
Built-in (irreplaceable)
Operation continues against power failure of
5ms or less.
−
Operation continues against power failure of 5ms or less.
FX
2NC
-32BL
(life: Approx. 3 years)
−
FX2NC-32BL
(life: Approx. 3 years)
0~50
°
C0~50
°
C0~40
°
C
35 to 85%RH (no condensation)
Free from corrosive gas and much dusts
In conformance to JIS B3502 and IEC 61131-2 (147 m/s
2
, 3 times in each of X, Y and Z directions)
By noise simulator of 1,000 Vp-p in noise voltage, 1
µ
s in noise width and 30 to 100 Hz in frequency
←
500V AC for 1 min
*5
500V AC for 1 min
(between all power terminals and ground terminal)
←
5 M
Ω
or more by 500V DC megger
*5
5 M
Ω
or more by 500V DC megger
(between all power terminals and ground terminal)
←
Grounding resistance
100
Ω
or less
−
Grounding resistance 100
Ω
or less
Equivalent to IP65f
*6*7
Equivalent to IP65f
*6*7
Equivalent to IP54
*6
Approx. 50,000 hours or more (working temperature: 25
°
C)
Guarantee period is 1 year.
50,000 hours
or more
−
40,000 hours or more
LED (Red/White)
Cold cathode tube (working temperature: 25
°
C)
Guarantee period is 1 year.
In conformance
to JIS B3502
and IEC 61131-2
Frequency Acceleration Amplitude
10 times in each
of X, Y and Z
directions
(for 80 min)
With intermittent
vibration
10~57Hz
−
0.075mm
57~150Hz 9.8m/s
2
−
With continuous
vibration
10~57Hz
−
0.035mm
57~150Hz 4.9m/s
2
−
Commenti su questo manuale